MC-Bauchemie MC-RIM PW 101

MC-BAUCHEMIEAuthorised distributor

MC-Bauchemie MC-RIM PW 101

A DVGW-tested mineral coating built for one job: keeping RCC reservoirs, water-treatment tanks and drinking-water infrastructure structurally sound and hygienically clean, layer after layer.

BrandMC-BauchemieCategoryProtective CoatingsFormMC-RIM PW 101 is a single-component, cement-bound mineral coating built on MC-Bauchemie’s DySC technology. It’s mixed…

What is it?

MC-RIM PW 101 is a single-component, cement-bound mineral coating built on MC-Bauchemie’s DySC technology. It’s mixed with nothing but water and applied in two to three passes by hand or wet-spray to build a dense, low-porosity barrier directly on concrete.

Where is it used?

Internal wall and overhead (soffit) surfaces of drinking water reservoirs, clear-water and clarified-water tanks at treatment plants, and RCC structures inside notified drinking-water protection zones – on both new-build work and rehabilitation of ageing tanks.

Why use it?

It’s tested and approved to DVGW leaflet W347 Type 2, meets DVGW W270 and W300-5(A), and carries ÖVGW certification with external monitoring – the reference points consultants ask for when a coating will permanently touch potable water. It’s also rated EN 1504-3 Class R4, so it performs like a structural repair mortar, not a thin decorative seal.

How is it applied?

Powder goes into water at a fixed 100:13-14 ratio (roughly 3.25-3.5 litres per 25kg bag) in a forced or double mixer – mixing by hand isn’t permitted. It’s built up in 2-3 layers of 8-15mm each, the first worked in as a scratch coat, trowel-finished and sponge-rubbed on the last pass, then cured at 85-95% relative humidity for three times the normal DIN 1045-3 period.

About MC-Bauchemie MC-RIM PW 101

Coatings that touch drinking water sit in a narrow, compliance-heavy category of their own. It isn’t enough for a lining to keep water out or in – it also has to not leach anything, not feed microbial growth, and survive years of fill/empty cycling, chlorination and variable water chemistry without breaking down. MC-RIM PW 101 was built specifically for that brief. It’s a rigid, non-crack-bridging mineral coating – meaning it’s engineered for sound RCC water-retaining structures where movement is controlled through proper joints, not for substrates expected to keep cracking under it. In exchange for that constraint it delivers genuine structural-mortar performance: EN 1504-3 Class R4, compressive strength of 45 N/mm² or higher at 28 days, and a water penetration depth of just 1mm at 5 bar – while staying open to vapour diffusion so trapped moisture doesn’t build up and blister the surface when a tank is drained for inspection.

For the Indian market, that lands squarely on municipal ESR/GSR/UGR reservoirs, WTP clear-water and clarified-water tanks, and industrial captive water-treatment structures – the kind of assets where an ordinary waterproofing coating simply isn’t specified to touch potable water, and where a consultant will ask for DVGW- or equivalent-referenced documentation before sign-off. Space Arc supplies and applies MC-RIM PW 101 as an authorised MC-Bauchemie distributor across Delhi NCR and pan-India, and we’d flag this upfront: the product’s tolerances are tight by design – fixed mixing ratio, mandatory machine mixing, a defined working-time window, and an actively maintained high-humidity curing regime – so it rewards being installed by a trained crew rather than treated as an off-the-shelf paint-on coating.

The technical insight

The “rigid, non-crack-bridging” classification is the detail specifiers most often skip past, and it’s the one that matters most on site. MC-RIM PW 101 is certified under EN 1504-3 for both principle 3 (structural restoration) and principle 7 (preserving/restoring passivity against ingress), procedures 3.1, 3.3 and 7.1. That combination means it does two jobs at once: rebuilding surface profile and strength on a repaired substrate, and forming a low-permeability, chemically resistant skin over it. What it isn’t doing is bridging live cracks – if the underlying RCC has structural movement, that needs to be resolved with joint detailing or a flexible system before MC-RIM PW 101 goes on, not covered over by it. On the drinking-water side, DVGW W347 Type 2 testing and W270/W300-5(A) compliance are German technical-standard references rather than an Indian statutory approval, so on regulated municipal contracts we recommend treating them as strong supporting documentation and getting explicit sign-off from the client’s own water authority or consulting engineer, rather than assuming automatic acceptance.

Where it is used

  • Elevated (ESR) and ground-level (GSR) service reservoirs for municipal water supply
  • Underground water storage reservoirs (UGRs) and clear-water sumps at treatment plants
  • Clarified/clear-water tanks and RCC process chambers inside water treatment plants (WTPs)
  • RCC concrete structures within notified drinking-water catchment/protection zones
  • Rehabilitation of ageing reservoirs showing leaching, honeycombing or carbonation before recommissioning
  • New-build RCC water-retaining structures where a hygienic internal lining is specified at design stage
  • Industrial captive water-treatment tanks in food, beverage and pharma facilities
  • Wall and soffit (overhead) surface protection inside enclosed potable-water structures

Key advantages

  • DVGW W347 Type 2 tested and W270/W300-5(A) compliant – built specifically not to leach substances into stored drinking water
  • EN 1504-3 Class R4 rated – compressive strength ≥45 N/mm² and flexural strength ≥6.5 N/mm² at 28 days, so it structurally reinforces the substrate rather than just sealing it
  • Water penetration of just 1mm at 5 bar, yet stays open to vapour diffusion – won’t trap moisture and blister when a tank is drained
  • Highly resistant to chlorides and sulphates, relevant given how variable raw and ground water chemistry can be across Indian sites
  • Cement-based, single-component system mixed only with water – simpler site QC than two-pack epoxy or PU systems, with no solvent/VOC handling
  • Documented coverage rate (1.9 kg/m²/mm) makes BOQ quantity estimation straightforward
  • ÖVGW-certified with external, third-party monitoring standing behind the manufacturer’s own quality claims

Limitations & considerations

  • Rigid and non-crack-bridging – not suitable where the substrate has active or moving cracks; those need joint treatment or a flexible system first
  • Application window is tight: air, substrate and material must all sit between 5°C and 30°C, which needs planning around peak summer surface temperatures
  • Curing is demanding, not optional – 85-95% relative humidity has to be actively maintained (humidifiers, not just wet hessian) for three times the standard DIN 1045-3 period, and it’s the step site teams most often shortcut
  • Minimum 8mm per pass means it’s a genuine coating build-up, not a thin skim – expect 2-3 work steps and more programme time than a roll-on liquid coating
  • Comes only in 25kg bags with no small touch-up pack, so wastage needs planning on small repair jobs

Selection & best practice

Treat substrate prep as non-negotiable – follow MC-Bauchemie’s General Application Advice for Fine Fillers, and confirm the concrete is sound, laitance-free and in a saturated surface-dry condition before the first pass. Batch strictly to the 100:13-14 powder-to-water ratio in a forced or double mixer for a full 5 minutes minimum; hand-mixing or splitting partial batches isn’t permitted. Work the first layer in hard as a scratch coat rather than laying it over the surface, leave the second layer spray-rough if you’re doing a three-pass build, and pre-smooth the final layer with a steel trowel before sponge-finishing it for density and impermeability. Respect the overcoating windows – about 30 minutes between the first and second layer, then either within 4 hours or after at least 16 hours between the second and third. The moment finishing is done, start curing: 85-95% relative humidity, sustained with air humidifiers, for three times the DIN 1045-3 period – this is where reservoir linings most often fail early, not in the material itself. Keep movement and construction joints out of scope for this coating; they need to be detailed and treated separately with a flexible joint system, not coated over rigidly.

Specifications

System / chemistry Cement-bound mineral coating (DySC-technology), single-component, mixed with water only
Mixing ratio 100 : 13–14 (powder : water, by weight); ≈3.25–3.50 L water per 25 kg bag
Coverage / consumption 1.9 kg/m² per mm of layer thickness (factory-dried mortar)
Layer thickness 8–15 mm per pass; 15 mm max total (may exceed locally by 25% on areas ≤5 m²)
Compressive strength (28 d) ≥45 N/mm²
Flexural strength (28 d) ≥6.5 N/mm²
Water penetration depth 1 mm at 5 bar gauge pressure (EN 12390-8, 28-day test age)
Standards / approvals EN 1504-3 Class R4 (principles 3 & 7, procedures 3.1/3.3/7.1); DVGW W347 Type 2, W270, W300-5(A); ÖVGW certified
Pack size / shelf life 25 kg bag; 12 months in cool, dry, unopened storage

Industry use cases

Municipal water utilities

Rehabilitating leaching or honeycombed ESR/GSR/UGR reservoirs so they can be recommissioned for potable supply

Water treatment plants

Lining clear-water and clarified-water tanks and RCC process chambers within the treatment train

Industrial captive water treatment

Protecting concrete process-water tanks in food, beverage and pharma plants where hygiene sign-off is required

PHED / state water board infrastructure

Refurbishing overhead and underground tanks under municipal supply-upgrade programmes

New-build reservoir construction

Specified at design stage by consulting engineers as the internal lining for new RCC water-retaining structures

Frequently asked questions

Is MC-RIM PW 101 actually safe for stored drinking water, or is that just marketing language?
It’s tested and approved to DVGW leaflet W347 Type 2 and meets DVGW W270 (hygiene/microbial growth) and W300-5(A), with ÖVGW certification backed by external monitoring – these are the German technical references specifiers rely on for potable-water-contact materials. On a regulated Indian municipal contract we’d still get the client’s water authority or consulting engineer to formally accept this documentation before it’s specified, since it isn’t an Indian statutory approval in itself.
Can it bridge cracks in an old reservoir wall?
No – it’s explicitly a rigid, non-crack-bridging coating. If the substrate has active or moving cracks, those need proper joint detailing or a flexible system first; coating over live cracks with MC-RIM PW 101 will just telegraph the crack back through the finish.
How much do we need for a typical reservoir job?
Consumption is 1.9 kg of factory-dried mortar per m² per mm of thickness, and the standard build is two to three layers up to 15mm total. So a 10mm build works out to roughly 19 kg/m² of powder before wastage – multiply that by your reservoir’s internal surface area to size the order in 25kg bags.
Does it need a primer before application?
The datasheet doesn’t call for a separate primer coat – the first pass itself is worked in as a scratch coat directly into a properly prepared substrate. Surface prep (soundness, laitance removal, saturated surface-dry condition) follows MC-Bauchemie’s general fine-filler application guidance and matters more than any primer would.
How is this different from a normal waterproofing coating we’d use on a terrace or basement?
General waterproofing coatings are engineered against water ingress from outside; this is engineered for water sitting permanently against it on the inside, plus a hygiene/leaching profile ordinary waterproofing products were never tested for. It also carries structural-mortar strength (EN 1504-3 R4) rather than behaving like a thin membrane, so it’s a different product category, not a premium version of the same one.
Can our regular painting contractor apply it, or does it need a specialist crew?
It’s cementitious, machine-mixed only, worked in multiple layers with defined overcoating windows, and needs actively maintained high-humidity curing – closer to a repair-mortar application than a paint job. We’d recommend a crew experienced with mineral coatings and repair mortars, which is why Space Arc offers it with application support rather than supply-only.

How we position MC-Bauchemie MC-RIM PW 101

Within MC-Bauchemie’s own range, MC-RIM PW 101 sits in the rigid, non-crack-bridging bracket of the company’s DySC-technology surface-protection coatings, alongside the firm’s broader family of mineral repair mortars and waterproofing systems that Space Arc carries for RCC rehabilitation work generally – useful context if a reservoir job needs structural patch repair before this coating goes on, not just the coating itself. Where a project genuinely needs crack-bridging flexibility instead of a rigid mineral build – say, a tank with a documented history of movement – Fosroc’s Nitocote CM210, a two-component elastomeric cementitious coating approved for potable water contact, is a realistic alternative we also stock, and specifiers should choose between the two on that movement question rather than on brand alone.

Preferred brand · Fosroc equivalent

Fosroc Nitocote CM210 — Specifiers who need crack-bridging flexibility from a two-component elastomeric cementitious coating – rather than MC-RIM PW 101’s rigid, DVGW-referenced mineral build – often turn to Nitocote CM210 instead, typically on tanks with a documented history of movement.

Compare with Fosroc Nitocote CM210 →

Source MC-Bauchemie MC-RIM PW 101 for your project

Authorised distribution, technical advice & professional application across Delhi NCR and Pan-India.


Scroll to Top