Master Builders Solutions Ucrete MF40AS
Smooth, flow-applied Ucrete polyurethane concrete with certified static control — the floor for electronics halls, pharma suites and solvent stores where a stray spark or discharge is not an option.
What is it?
An antistatic grade of Ucrete heavy-duty polyurethane concrete: a smooth, seamless, flow-applied floor finish laid at 4–6 mm over a conductive primer and copper earthing grid.
Where is it used?
Electronics and component assembly, pharmaceutical production and cleanrooms, laboratories, dry-process food and packing halls, and solvent or powder-handling areas in explosion-hazard zones.
Why use it?
It pairs Ucrete’s chemical and impact resistance with verified ESD performance — resistance-to-ground below 1 × 10⁶ ohm and body-voltage generation under 100 V — in one dense, impervious floor.
How is it applied?
Installed by trained applicators: prepared concrete, earthing points and copper tape grid, conductive primer, then the pigmented wearing body flow-applied at 8–14 kg/m² depending on thickness.
About Master Builders Solutions Ucrete MF40AS
Ucrete MF40AS from Master Builders Solutions is the antistatic member of the Ucrete MF family — the same dense polyurethane concrete that has protected aggressive process floors for decades, reformulated to bleed static charge safely to earth. Laid at 4 to 6 mm, it gives a smooth, seamless, easy-clean surface in a usefully wide colour palette, including the lighter greys and creams that electronics and pharma clients increasingly specify for bright, auditable production spaces.
For Indian facilities, the case is practical. Component-level ESD damage rarely announces itself at the line; it shows up months later as field failures and warranty claims. A floor that holds resistance-to-ground below 1 × 10⁶ ohm and keeps body-voltage generation under 100 V removes the largest uncontrolled surface in the room from that risk equation. Because the binder is Ucrete rather than a conventional epoxy, the same floor also shrugs off acid and alkali spillage, solvent wipe-downs, pallet-truck impact and service temperatures from −15 °C to +70 °C. Space Arc Engineering supplies the full system and installs it through trained crews across Delhi NCR and pan-India.
The technical insight
Static control here is a system, not a coating. Copper earthing tape is bonded to the building’s earth points and laid as a grid across the slab, then locked in with a conductive primer that forms a continuous equipotential plane. The MF40AS wearing body above it carries conductive media distributed through the polyurethane concrete matrix, so charge generated at the surface — footfall, trolley wheels, powder movement — finds a low-resistance path down to the grid faster than it can accumulate. That is why the floor is verified two ways: resistance-to-ground (below 1 × 10⁶ ohm, testable to EN 1081) and body-voltage generation (below 100 V on a walking person), meeting BS 5958, DIN 51953 and EN 61340 requirements. Mechanically, the PU-concrete chemistry cures to around 50 N/mm² compressive strength but with a lower elastic modulus than epoxy, so point loads and dropped tooling deform the floor microscopically instead of cracking it.
Where it is used
- Electronics, PCB and component assembly halls operating as ESD-protected areas
- Pharmaceutical production suites, packing halls and cleanroom corridors
- Solvent stores, charging rooms and powder-handling bays in explosion-hazard classified zones
- Laboratories and QC areas handling flammable reagents
- Dry-process food manufacturing and packaging floors
- Warehouses and dispatch zones serving static-sensitive inventory
- Refurbishment of failed epoxy ESD floors where chemical attack or impact was the cause
Key advantages
- Certified static performance: resistance-to-ground below 1 × 10⁶ ohm and body-voltage generation under 100 V, meeting BS 5958, EN 1081, DIN 51953 and EN 61340
- Ucrete chemical resistance — withstands a broad register of acids, alkalis and solvents, including spillage and discharge up to +70 °C
- Serves from −15 °C freezer conditions to +70 °C without losing grip on the substrate
- High mechanical strength (about 50 N/mm² compressive) with a resilient, low-modulus matrix that absorbs impact and point loads
- Fast programmes: tolerant of 7-day-old and damp (properly prepared) concrete, with return to light traffic inside 24 hours at +18 °C
- Dense, impervious, seamless finish that cleans easily and does not harbour bacteria
- Bfl-s1 reaction-to-fire classification to EN 13501-1
- Available in light, bright colours — a genuine step forward for antistatic PU-concrete floors
Limitations & considerations
- ESD performance depends on the whole build-up — earthing grid, conductive primer and wearing layer installed correctly. It is not a paint-on antistatic coating and should only go down through trained applicators.
- Intended for predominantly dry process areas; for wet production with heavy thermal shock and steam cleaning, a thicker textured grade such as Ucrete UD200 is the better specification.
- The smooth R10 surface suits dry traffic. Where oils, fats or wet processes create slip risk, choose a profiled Ucrete grade instead.
- Upper service limit is +70 °C — hot-oil discharge or steam above this needs a heavier Ucrete system, not MF40AS.
- Requires a sound substrate of roughly 30 N/mm² compressive strength; weak screeds must be removed before installation.
- Certified EPAs need periodic resistance verification after handover — budget for routine ESD audits, not just the installation.
Selection & best practice
Start with the drawing, not the mixer: agree earthing-point locations with the electrical contractor and lay the copper tape grid to the approved plan, because it cannot be corrected once the floor is down. Prepare the slab by captive shot-blasting to remove laitance and expose sound concrete of at least 30 N/mm², then vacuum thoroughly. Apply the conductive primer as a continuous, unbroken film over the grid — pinholing here is the most common cause of failed resistance readings. Mix full pre-weighed kits only; never split packs or adjust with solvent. Flow-apply the wearing body at 4 mm (8–10 kg/m²) or 6 mm (12–14 kg/m²), maintaining a wet edge for a seamless finish. Before handover, test resistance-to-ground across a measurement grid per EN 1081 and record the readings — that certificate is what your client’s ESD auditor will ask for.
Specifications
| Chemistry | Antistatic heavy-duty polyurethane concrete (Ucrete), flow-applied |
| Applied thickness | 4–6 mm |
| Consumption (wearing layer) | 8–10 kg/m² at 4 mm; 12–14 kg/m² at 6 mm |
| Compressive strength (28 d, +23 °C) | Approx. 50 N/mm² |
| Flexural / tensile strength | Approx. 20 N/mm² / 9 N/mm²; adhesion >2.0 N/mm² (concrete failure) |
| Electrical performance | Resistance-to-ground <1 × 10⁶ ohm; body-voltage generation <100 V |
| Service temperature | −15 °C to +70 °C |
| Slip / fire rating | R10 (wet PTV 35); Bfl-s1 to EN 13501-1 |
| Return to service | Light traffic within 24 h at +18 °C (accelerated option ~4 h at +15 °C) |
Industry use cases
Electronics & Component Manufacturing
Assembly halls and test bays run as ESD-protected areas, where the floor forms the primary discharge path and keeps body voltage on operators below damage thresholds for sensitive devices.
Pharmaceutical & Cleanroom
Production suites and packing halls needing a seamless, impervious, easily validated floor that also controls charge around powder handling and sensitive instrumentation.
Hazardous & Solvent-Handling Areas
Solvent stores, mixing rooms and classified zones where dissipating static safely to earth removes an ignition source, with Ucrete’s solvent resistance handling the spillage itself.
Food & Beverage (Dry Process)
Flour, powder and dry-blending areas where dust clouds carry explosion risk and hygiene demands a dense, joint-free surface that cleans fast between shifts.
Warehousing & Logistics for Electronics
Storage and dispatch floors for static-sensitive inventory, taking pallet-truck traffic and point loads without losing conductivity or cracking.
Frequently asked questions
Is Ucrete MF40AS antistatic or conductive, and what do the numbers mean?
How much material do I need per square metre?
Can it be laid on new or damp concrete?
How soon can production restart after installation?
When should I choose MF40AS over standard Ucrete MF or an epoxy ESD floor?
Does Space Arc install the earthing system too?
How we position Master Builders Solutions Ucrete MF40AS
Within the Master Builders Solutions family, MF40AS sits between standard Ucrete MF — the same smooth 4–6 mm floor without static control, for general dry process areas — and the heavy-duty grades: Ucrete UD200 for wet production with thermal shock and steam cleaning, and profiled Ucrete DP grades where slip resistance governs. For light-duty dry rooms on tighter budgets, MasterTop epoxy self-levellers are the honest downgrade. Among our other brand lines, Sikafloor ESD epoxy systems suit server rooms and electronics stores with lighter mechanical duty, while Fosroc Nitoflor covers general industrial floors without ESD needs. Space Arc supplies and installs all of these, so specify by exposure, not by habit — call us to match the grade to the room.